We understand that appropriate sizing of HVAC Equipment is critical for the design of energy efficient HVAC system at optimum cost. Hence we adopt a systematic approach towards HVAC sizing, taking into consideration various such as climate, building configuration, space usage, system zoning and layouts. Our systems comply with ASHRAE, National Building Codes & Energy Conservation Building Codes.

We plan the fire - fighting and fire-protection systems in accordance with AHJ (Authority Having Jurisdiction) standards, and\or international standards such as NFPA or FM.

Water is stored in underground fire reserve tank of the stipulated and is drawn using electrically driven jockey pumps, fire pumps or sprinkler pump. All pumps have a separate suction line from the fire suction header.

Delivery from the pumps is connected to the respective hydrant and sprinkler system, for which installation control valves with hydraulic alarm are provided in the basement. The sprinkler pump is isolated from the main discharge header by a no-return valve so that the hydrant pump can also act as standby for the sprinkler system.

The pumps are designed to maintain a pressure of 3.5kg\Sq.cm at the farthest hydrant. A standby diesel engine driven fire pump of the same capacity is installed as back-up for the electrically operated fire hydrant/sprinkler pump, as per fire regulations.

Independent jockey pumps for hydrant and sprinkler system operate intermittently in order to take care of hydraulic losses in the system and maintain the minimum pressure respectively in wet risers and sprinkler system. Fire pump rating is in accordance with AHJ directive and also caters to future expansion requirement.

Electrical system are designed as per project requirement and in accordance with all relevant local and international codes to have fault free system minimum maintenance and max safety and savings.

Integrated Building Management System (IBMS) is designed in building to have a central command and information of various equipments/item in the building e.g. HVAC Electrical, Plumbing, Fire Fighting Security, Lifts, Elevators and many more. It helps in saving the manpower, energy and facilitates information system.